Light Metal Ex-Plugs and Sockets
16 A metal design for zone 1 and 2
The explosion-protected light metal plugs and receptacle devices can be used in the areas of Zone 1 and Zone 2 at no risk of explosion. Extremely harsh conditions of use in the hazardous area requires the devices to have highest mechanical strength. The explosion-protected CEAG plug and socket devices can be used to supply the appropriate energy to portable electrical equipment in these harsh conditions. The robust plug and receptacle devices with high-quality cast aluminium housings can be connected to a large connecting room via explosion-proof conduits or explosion-proof screwed connections.
Flameproof enclosure
Unused flameproof threads for cable glands have to be closed with certified plugs. The light metal plug and socket devices have an outside earthing connection. The explosion-protected plug can be plugged into an industrial sockets if their contacts are executed according to IEC 60309. Connecting terminals are in an Ex-e chamber, all other parts are Ex-d protected.
- Ex-d enclosure
- High mechanical, chemical and thermal resistance conduit
- Connecting technology
- Type 16 A 3-pole
- Type 16 A 4-pole
- Type 16 A 5-pole